Consumer Unit Sizing Calculator — How Many Ways Do I Need?

Calculate the right consumer unit size for your property based on BS 7671 18th Edition. Includes spare ways for future expansion.

Preset loads typical circuits automatically

20% recommended for future expansion

Cooker circuit

32A dedicated circuit for electric cooker

Electric shower circuit

40A dedicated circuit for electric shower

Immersion heater

16A dedicated circuit

EV charger

32A dedicated circuit for 7kW charger

Intruder alarm / CCTV

6A dedicated circuit

Outdoor socket / lighting

16A dedicated circuit

Underfloor heating

16A dedicated circuit

Smoke / heat detectors

6A dedicated circuit — required by Building Regs

How We Calculate This

This calculator determines the consumer unit size you need by counting all required circuits for your property and adding spare ways for future expansion, following BS 7671 18th Edition guidelines.

The formula

Total ways = Number of circuits + Spare ways (min 20% or 2 ways)

The calculator then rounds up to the nearest standard consumer unit size available in the UK: 6, 10, 12, 16, 18, or 21 ways.

Standard UK circuit MCB ratings

  • Lighting circuits: 6A Type B MCB
  • Ring main (sockets): 32A Type B MCB
  • Cooker circuit: 32A Type B MCB
  • Electric shower: 40A Type B MCB (for up to 9.5kW)
  • Immersion heater: 16A Type B MCB
  • EV charger (7kW): 32A Type B MCB
  • Smoke detectors: 6A Type B MCB