Skip to content

Heat Loss Calculator \u2014 Room-by-Room Heating Requirements

Calculate fabric and ventilation heat losses for any room to correctly size radiators and heating systems. Uses UK CIBSE design conditions (21\u00B0C inside, -1\u00B0C outside).

Room Dimensions

Standard UK ceiling: 2.4m


External Exposure

Walls facing outside

Average window area on each external wall

Doors to outside


Construction U-Values


Air changes per hour \u2014 depends on draught-proofing and ventilation system

How We Calculate This

This calculator uses the standard CIBSE (Chartered Institution of Building Services Engineers) method for calculating room heat loss, which underpins heating system design across the UK.

Fabric heat loss formula

Fabric heat loss (W) = Σ(Area × U-value × ΔT)

Each building element (walls, windows, doors, roof, floor) contributes heat loss based on its area, U-value, and the temperature difference between inside and outside (ΔT = 22K for standard UK conditions: 21°C inside, -1°C outside).

Ventilation heat loss formula

Ventilation heat loss (W) = 0.33 × Volume × Air changes per hour × ΔT

The 0.33 factor comes from the volumetric heat capacity of air (1,200 J/m³K divided by 3,600 seconds). Air changes per hour (ACH) represents how many times the room's air volume is replaced each hour through draughts and ventilation.

Total heat loss

Total = Fabric heat loss + Ventilation heat loss

The total heat loss in Watts is the heating output required to maintain the design temperature. This is used to select the correct radiator size or heating system output for the room.

Frequently Asked Questions

Last updated: February 2026

All calculations are estimates. Verify with your supplier.