Insulation Thickness Calculator \u2014 How Much Insulation Do I Need?

Calculate the insulation thickness needed to meet UK Building Regulations Part L for walls, roofs and floors.

Building Regs default shown. Adjust if needed.

How We Calculate This

This calculator determines the insulation thickness required to achieve a target U-value for your building element. It uses the standard thermal resistance calculation method from BS EN ISO 6946 and references UK Building Regulations Approved Document L.

The formula

Required insulation R = (1 / target U-value) - Rsi - Rse - existing construction R

Insulation thickness = R × thermal conductivity × 1000 (mm)

For example, to achieve 0.30 W/m²K on a cavity wall (base R = 0.45) with mineral wool (0.035 W/mK): Required R = (1/0.30) - 0.13 - 0.04 - 0.45 = 2.71 m²K/W. Thickness = 2.71 × 0.035 × 1000 = 95mm.

Building Regulations Part L targets

  • External walls: 0.30 W/m²K
  • Pitched roof: 0.16 W/m²K
  • Flat roof: 0.18 W/m²K
  • Ground floor: 0.25 W/m²K

The thickness is rounded up to the nearest 5mm to match standard product sizes. Always check manufacturer datasheets for exact lambda values, as these can vary slightly between products.

Frequently Asked Questions

Last updated: February 2026

All calculations are estimates. Verify with your supplier.