Soakaway Sizing Calculator — UK Building Regs Part H

Size a soakaway to UK BRE DG 365 standards. Calculate the required volume based on your roof and paved area, soil type and UK rainfall rates.

Plan area of roof draining to this soakaway

Patio, driveway, etc. draining to this soakaway

Infiltration rate: 3.6 mm/hr

How We Calculate This

Our soakaway calculator uses the methodology from BRE Digest 365 and UK Building Regulations Approved Document Part H to estimate the required soakaway volume for your property.

The design method

The soakaway must store the volume of rainwater that falls during a design storm (30 minutes at 50mm/hr — the UK standard) minus what drains away through the soil during that time.

Required Volume = (Drainage Area × Rainfall Rate × Storm Duration) - Infiltration

Design parameters

  • Design rainfall rate: 50 mm/hr (UK standard for soakaway design)
  • Storm duration: 30 minutes
  • Sand/gravel infiltration: 36 mm/hr
  • Loam infiltration: 3.6 mm/hr
  • Clay infiltration: 0.36 mm/hr

Important notes

  • Soakaways must be at least 5m from any building (Part H requirement)
  • Crate soakaways have ~95% void ratio; rubble fill has only ~30%
  • A site-specific percolation test is essential for accurate results
  • This calculator provides estimates — always consult Building Control