UK Cable Sizes & Current Ratings — BS 7671 Reference

Selecting the correct cable size is a fundamental part of electrical installation design in the UK. This reference page covers the standard cable sizes used in domestic and light commercial installations, their current-carrying capacities under BS 7671 (18th Edition), and the typical circuits they serve.

Twin and Earth (6242Y) Current Ratings

Flat twin and earth cable (6242Y) is the standard cable for domestic wiring in the UK. Current ratings below are for Reference Method C (clipped direct to a surface) from BS 7671 Table 4D5:

Cable Size (mm²)Current Rating (Method C)CPC SizeCommon Circuit
1.0 mm²15.5 A1.0 mm²Lighting circuits (6 A MCB)
1.5 mm²20 A1.0 mm²Lighting circuits (longer runs), immersion heater (on short run)
2.5 mm²27 A1.5 mm²Ring final circuits (32 A), radial sockets (20 A)
4.0 mm²37 A1.5 mm²Cooker circuit (small), immersion heater, storage heater
6.0 mm²47 A2.5 mm²Cooker circuit (standard), shower (up to 9.5 kW)
10.0 mm²65 A4.0 mm²Shower (10.5–11.5 kW), large cooker, EV charger
16.0 mm²87 A6.0 mm²Sub-main to outbuilding, large EV charger, meter tails

Current ratings shown are for Reference Method C (clipped direct). Ratings reduce for Method A (enclosed in insulation) or Method B (enclosed in conduit/trunking). Always apply correction factors for grouping, ambient temperature, and thermal insulation.

Common Domestic Circuits

CircuitMCB RatingCable SizeNotes
Lighting6 A Type B1.0 mm² or 1.5 mm²Max 12 points per circuit (common practice)
Ring final (sockets)32 A Type B2.5 mm²Max 100 m² floor area served
Radial sockets20 A Type B2.5 mm²Max 50 m² floor area served
Immersion heater16 A Type B2.5 mm²Dedicated radial circuit, unswitched fused spur
Cooker32 A Type B6.0 mm²Via cooker control unit with 13 A socket
Electric shower (9.5 kW)40 A Type B6.0 mm² or 10.0 mm²Depends on run length and voltage drop
EV charger (7 kW)32 A Type B6.0 mm² or 10.0 mm²Depends on run length; PEN fault protection required

Key Points for Cable Selection

  • Current-carrying capacity — The cable must carry the design current without overheating. Apply correction factors for ambient temperature, grouping, and thermal insulation.
  • Voltage drop — BS 7671 limits voltage drop to 3% for lighting and 5% for other circuits. Longer cable runs may need upsizing to stay within limits.
  • Fault current — The CPC (earth) must carry the earth fault current long enough for the protective device to operate. Check adiabatic equation where required.
  • Installation method — How the cable is installed affects its current rating. Cables buried in insulation can carry significantly less current than those clipped to a surface.

Calculate Your Cable Requirements

Current ratings are extracted from BS 7671:2018+A2:2022 (18th Edition). This reference is for guidance only and does not replace the need for proper cable sizing calculations by a qualified electrician. All domestic electrical work must comply with Part P of the Building Regulations.